Install and maintain emergency lighting for use in a power failure.


CONTROL ID
01440
CONTROL TYPE
Physical and Environmental Protection
CLASSIFICATION
Preventive

SUPPORTING AND SUPPORTED CONTROLS




This Control directly supports the implied Control(s):
  • Employ environmental protections., CC ID: 12570

There are no implementation support Controls.


SELECTED AUTHORITY DOCUMENTS COMPLIED WITH




  • F42: The organization shall install emergency lighting and portable lighting fixtures in the computer room. F114: The organization shall install lighting fixtures and emergency lighting systems in ATM rooms to allow monitoring from outside to prevent crimes. F114.2: The organization should install e… (F42, F114, F114.2, FISC Security Guidelines on Computer Systems for Banking and Related Financial Institutions, 7th Edition)
  • It is desirable to allow the aisle to be evacuated in two directions. In addition, it is necessary to provide signs and lighting so that evacuations can also take place safely at night. Furthermore, keep the emergency exits and refuge passages neat, clean, organized, and uncluttered, with attention … (F3.2., FISC Security Guidelines on Computer Systems for Financial Institutions, Ninth Edition, Revised March 2020)
  • Emergency exits must be installed on the evacuation passage inside the room at two or more places. For large computer rooms, it is necessary to divide the room into several sections, set an evacuation route for each section, and install guide lights and guide signs to emergency exits. (F30.1. ¶ 1(1), FISC Security Guidelines on Computer Systems for Financial Institutions, Ninth Edition, Revised March 2020)
  • It is necessary to provide computer rooms with emergency lighting equipment and portable lighting equipment. (F42.1. ¶ 1, FISC Security Guidelines on Computer Systems for Financial Institutions, Ninth Edition, Revised March 2020)
  • Also in an ATM room managed and operated unattended, the installed emergency electric lighting system should be properly operated with the emergency power generator. (F108.2. ¶ 1, FISC Security Guidelines on Computer Systems for Financial Institutions, Ninth Edition, Revised March 2020)
  • In ATM rooms that are managed unattended, it is recommended to install proper emergency lighting systems to ensure security even in the event of power failure. (F114.2., FISC Security Guidelines on Computer Systems for Financial Institutions, Ninth Edition, Revised March 2020)
  • The power supply to critical facilities should be protected by installing emergency lighting in case of main power failure. (CF.19.02.02d, The Standard of Good Practice for Information Security)
  • The power supply to critical facilities should be protected by installing emergency lighting in case of main power failure. (CF.19.02.02d, The Standard of Good Practice for Information Security, 2013)
  • If the main power fails, emergency lighting should be available. (§ 9.2.2, ISO 27002 Code of practice for information security management, 2005)
  • The organization employs and maintains automatic emergency lighting for the information system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Control, StateRAMP Security Controls Baseline Summary Category 3, Version 1.1)
  • The organization employs and maintains automatic emergency lighting for the information system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Control, StateRAMP Security Controls Baseline Summary High Sensitivity Level, Version 1.1)
  • The organization must implement and maintain emergency lighting systems that automatically activate in case of a power disruption or outage and that cover emergency exits and evacuation routes. (CSR 5.1.5, Pub 100-17 Medicare Business Partners Systems Security, Transmittal 7, Appendix A: CMS Core Security Requirements CSR, March 17, 2006)
  • An automatic emergency lighting system must be installed for evacuation routes and emergency exits. (PEEL-1, DoD Instruction 8500.2 Information Assurance (IA) Implementation)
  • An automatic emergency lighting system must be installed for all areas that are needed for maintaining business essential functions, mission essential functions, and for evacuation routes and emergency exits. (PEEL-2, DoD Instruction 8500.2 Information Assurance (IA) Implementation)
  • The emergency lighting should be tested frequently and should automatically start when it is needed. (Protective Lighting, DOT Physical Security Survey Checklist)
  • Activation of automated emergency lighting of critical infrastructure, evacuation routes, and emergency exits. (App A Objective 13:9d Bullet 9, FFIEC Information Technology Examination Handbook - Architecture, Infrastructure, and Operations, June 2021)
  • The organization employs and maintains automatic emergency lighting for the information system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 High Baseline Controls, FedRAMP Baseline Security Controls, 8/28/2018)
  • The organization employs and maintains automatic emergency lighting for the information system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Moderate Baseline Controls, FedRAMP Baseline Security Controls, 8/28/2018)
  • The organization employs and maintains automatic emergency lighting for the information system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Low Baseline Controls, FedRAMP Baseline Security Controls, 8/28/2018)
  • Employ and maintain automatic emergency lighting for the system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Control, FedRAMP Security Controls High Baseline, Version 5)
  • Employ and maintain automatic emergency lighting for the system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Control, FedRAMP Security Controls Low Baseline, Version 5)
  • Employ and maintain automatic emergency lighting for the system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Control, FedRAMP Security Controls Moderate Baseline, Version 5)
  • Employ and maintain automatic emergency lighting for the system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Control, Control Baselines for Information Systems and Organizations, NIST SP 800-53B, High Impact Baseline, October 2020)
  • Employ and maintain automatic emergency lighting for the system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Control, Control Baselines for Information Systems and Organizations, NIST SP 800-53B, Low Impact Baseline, October 2020)
  • Employ and maintain automatic emergency lighting for the system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Control, Control Baselines for Information Systems and Organizations, NIST SP 800-53B, Moderate Impact Baseline, October 2020)
  • Physical and Environmental Protection (PE): Organizations must: (i) limit physical access to information systems, equipment, and the respective operating environments to authorized individuals; (ii) protect the physical plant and support infrastructure for information systems; (iii) provide supporti… (§ 3, FIPS Pub 200, Minimum Security Requirements for Federal Information and Information Systems, March 2006)
  • Organizational records, documents, and the facility should be examined to ensure an emergency lighting system is installed and starts automatically when a power outage occurs; the emergency lighting covers the emergency exits and evacuation routes; the emergency lighting system has been tested and f… (PE-12, Guide for Assessing the Security Controls in Federal Information Systems, NIST SP 800-53A)
  • The organization employs and maintains automatic emergency lighting for the information system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Control: Low Baseline Controls, Guide to Industrial Control Systems (ICS) Security, Revision 2)
  • The organization employs and maintains automatic emergency lighting for the information system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Control: Moderate Baseline Controls, Guide to Industrial Control Systems (ICS) Security, Revision 2)
  • The organization employs and maintains automatic emergency lighting for the information system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Control: High Baseline Controls, Guide to Industrial Control Systems (ICS) Security, Revision 2)
  • The organization must use and maintain automatic emergency lighting that activates during a power outage or disruption and covers emergency exits and evacuation routes. (App F § PE-12, Recommended Security Controls for Federal Information Systems, NIST SP 800-53)
  • The organization should provide emergency lighting for all areas that support essential missions and business functions. (App F § PE-12(1), Recommended Security Controls for Federal Information Systems, NIST SP 800-53)
  • The organization employs and maintains automatic emergency lighting for the information system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Control, Security and Privacy Controls for Federal Information Systems and Organizations, NIST SP 800-53, Deprecated, Revision 4, Deprecated)
  • The organization provides emergency lighting for all areas within the facility supporting essential missions and business functions. (PE-12(1), Security and Privacy Controls for Federal Information Systems and Organizations, NIST SP 800-53, Deprecated, Revision 4, Deprecated)
  • The organization employs and maintains automatic emergency lighting for the information system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Control, Security and Privacy Controls for Federal Information Systems and Organizations, NIST SP 800-53, High Impact Baseline, Deprecated, Revision 4, Deprecated)
  • The organization employs and maintains automatic emergency lighting for the information system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Control, Security and Privacy Controls for Federal Information Systems and Organizations, NIST SP 800-53, Low Impact Baseline, Deprecated, Revision 4, Deprecated)
  • The organization employs and maintains automatic emergency lighting for the information system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Control, Security and Privacy Controls for Federal Information Systems and Organizations, NIST SP 800-53, Moderate Impact Baseline, Deprecated, Revision 4, Deprecated)
  • The organization employs and maintains automatic emergency lighting for the information system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Control, Security and Privacy Controls for Federal Information Systems and Organizations, NIST SP 800-53, High Impact Baseline, Revision 4)
  • The organization employs and maintains automatic emergency lighting for the information system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Control, Security and Privacy Controls for Federal Information Systems and Organizations, NIST SP 800-53, Low Impact Baseline, Revision 4)
  • The organization employs and maintains automatic emergency lighting for the information system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Control, Security and Privacy Controls for Federal Information Systems and Organizations, NIST SP 800-53, Moderate Impact Baseline, Revision 4)
  • The organization employs and maintains automatic emergency lighting for the information system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Control, Security and Privacy Controls for Federal Information Systems and Organizations, NIST SP 800-53, Revision 4)
  • The organization provides emergency lighting for all areas within the facility supporting essential missions and business functions. (PE-12(1) ¶ 1, Security and Privacy Controls for Federal Information Systems and Organizations, NIST SP 800-53, Revision 4)
  • Provide emergency lighting for all areas within the facility supporting essential mission and business functions. (PE-12(1) ¶ 1, Security and Privacy Controls for Information Systems and Organizations, NIST SP 800-53, Revision 5)
  • Employ and maintain automatic emergency lighting for the system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Control, Security and Privacy Controls for Information Systems and Organizations, NIST SP 800-53, Revision 5)
  • Provide emergency lighting for all areas within the facility supporting essential mission and business functions. (PE-12(1) ¶ 1, Security and Privacy Controls for Information Systems and Organizations, NIST SP 800-53, Revision 5.1.1)
  • Employ and maintain automatic emergency lighting for the system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Control, Security and Privacy Controls for Information Systems and Organizations, NIST SP 800-53, Revision 5.1.1)
  • The organization employs and maintains automatic emergency lighting for the information system that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility. (PE-12 Control, TX-RAMP Security Controls Baseline Level 2)